RCD vs RCBO: the difference and which one to choose
An RCD guards against leakage current, a breaker guards the cable against overload. Here is where an RCBO fits, how 30 mA differs from 300 mA and what to ask your electrician.
In brief
An RCD cuts the line when part of the current escapes outside the wires, for example through a person or into the wet casing of a washing machine. A circuit breaker does not notice this: it protects the cable against overload and short circuit. An RCBO is a breaker and an RCD in one housing.
An RCD is not installed on its own, because nothing would protect it from overload. For protecting people, use a 30 mA device.
What the breaker does and what the RCD does
The breaker watches the size of the current. If the cable carries too many amps, it trips before the wire heats up. Ratings are covered in our article on choosing a breaker.
The RCD watches the balance: whatever current leaves along the phase must come back along the neutral. If some of it leaks away through insulation, an earthed casing or a person, the difference passes the threshold and the RCD opens the circuit within a fraction of a second. The current in the line can be quite small, and a breaker would not react.
That is why in a board they work as a pair: the breaker catches overload and short circuit, the RCD catches leakage. One does not replace the other.
30 mA or 100 and 300 mA
The figure on the housing is the leakage current at which the RCD trips. 30 mA is protection of people against electric shock, and it goes on sockets, the kitchen, the bathroom and the water heater.
RCDs of 100 and 300 mA do not protect people from shock. They sit at the incoming supply or ahead of several boards to disconnect a serious leak that could start a fire, often together with 30 mA devices further down. In a flat the main choice is 30 mA.
An RCD is an extra layer, not a reason to relax: do not touch sockets or faulty appliances with wet hands, even if a 30 mA RCD is installed.
Type AC or type A
Type AC responds to sinusoidal alternating leakage. Type A also responds to a pulsating direct component produced by appliances with electronics: inverter washing machines, induction hobs, chargers.
Type A is chosen more often for the kitchen, the washing machine and an electric car charger. For a specific appliance, read its manual. The type is usually marked on the housing with a symbol: a wave for AC, a wave with a half-wave for A.
There is also type B, which senses smooth direct current too; it is required for some charging stations and industrial equipment. In a flat it is usually not needed.
Why an RCD needs a breaker
A breaker goes ahead of the RCD, or you use an RCBO. The reason is that an RCD does not count amps: under overload or a short circuit it can fail before the protection upstream reacts.
The RCD rating is the current it is allowed to carry continuously. It must be at least the rating of the breaker in front of it. Hence a frequent mistake: a 32 A breaker and a 25 A RCD.
An RCBO does not have this problem: protection against overload and short circuit is built in, so there is no pair of ratings to match. You choose the rating by the cable and the leakage current, usually 30 mA.
Where each goes in a flat
A typical scheme: a main breaker, then a 30 mA RCD, and a separate breaker for every line. One RCD for the whole flat is cheaper, but a leak on one line switches off every room and the cause is harder to find.
So the lines are split: an RCD for the sockets and the kitchen, a separate device for the bathroom, water heater and washing machine, and lighting on its own. An RCBO on each important line settles the question: when it trips, you know which line has the fault. It takes 1–2 modules and costs more than a breaker plus RCD pair.
The washing machine and the water heater in the bathroom are often given their own 30 mA RCD or RCBO. Then a leak in one appliance does not switch off the other, and the cause is found quickly.
Typical mistakes: what to ask the electrician
Ask how the neutral is wired: the neutral of a line protected by one RCD must not be joined to the neutral of another RCD or to a common bar. Otherwise the RCD trips for no visible reason.
Ask where neutral and earth are joined: downstream of the RCD they must stay separate. Find out what load each line carries, because too many appliances on one RCD add up their leakage and give false trips.
Check whether the building has an earth conductor. An RCD can trip without one when current flows through a person, but it does not replace earthing. Wiring is done by a licensed electrician following local rules. And ask to see the Test button: pressing it regularly, say once a month, is good practice.
After installation ask the electrician to show the test result: RCD operation is checked with an instrument, and the reading can be written down.
What the catalog offers
The Xkoren XKR6 two-pole RCD, 30 mA, comes in 25, 32, 40 and 63 A, about 34.5 ₾ for any rating. The name does not state type AC or A, so check the marking on the housing.
Breakers for it: Xkoren XKN6 C16, 6 kA, about 5.8 ₾; LEGRAND XS3 B16, about 6.4 ₾; XS3 C16, about 7.8 ₾; two-pole LEGRAND XG3 C16, 6 kA, about 32.9 ₾. The catalog also has the LEGRAND 03006180 RCBO, 63 A, 30 mA (listed as 2K 63A 30MA), about 91.1 ₾. An enclosure for 12 modules, such as the plastic Almera, is about 15.9 ₾. Electrical goods are sold by the pack: the price is per unit, see the product page for the number of units in a pack.
Checklist before buying
Decide where leakage protection is needed: sockets, kitchen, bathroom, water heater, washing machine. Choose the leakage rating: 30 mA for people. Pick an RCD rating not below the rating of the breaker ahead of it. Check the type in the appliance manuals: equipment with electronics often needs type A.
Decide whether to put one RCD on several lines or RCBOs on the important ones. On a single-phase supply take two-pole devices, which break both phase and neutral. Count modules: a two-pole RCD takes 2 places in the board. Send a diagram or a photo of your board to the chat on the site or to the Telegram bot @Asbtrade_ge_bot and we will check the set; the electrician confirms the final scheme.
Related products
- Xkoren XKR6 residual current device (RCD) 2P, 30 mA, 25 A
- Xkoren XKR6 residual current device (RCD) 2P, 30 mA, 40 A
- Xkoren XKN6 miniature circuit breaker 1P, C curve, 16 A, 6 kA
- LEGRAND XS3 1K B16 4.5KA circuit breaker
- LEGRAND XS3 1K C 16 4.5KA circuit breaker
- LEGRAND XG3 2K C 16 6 KA circuit breaker
- Almera plastic distribution board, 12 modules
- Almera plastic distribution board, 9 modules
Frequently asked questions
Can an RCD be installed without a breaker?
No. An RCD does not protect against overload or short circuit, so it needs a breaker ahead of it with a rating not above the RCD rating, or you fit an RCBO.
Which leakage rating suits a flat?
For protecting people, 30 mA on the sockets, kitchen, bathroom and water heater. RCDs of 100 and 300 mA do not protect against electric shock.
How does type A differ from type AC?
Type A also trips on the pulsating direct component of leakage current produced by appliances with electronics. Read the manual of the specific appliance for its requirements.
Why does the RCD trip for no visible reason?
Common causes are a faulty appliance with small leakage, too many appliances on one RCD, or the neutrals of different lines joined together. The electrician finds the cause with a test instrument.
Which is better: RCD with breaker or an RCBO?
An RCBO takes less space and shows which line has the fault. A breaker plus RCD pair is cheaper, and one RCD can serve a group of lines.