ASB Trade › Cable and trunking › Fire-resistant cables
Fire-resistant cables
4 items · ASB, Unifire
- HUNKAKABLO J-Y(ST) Y (2X2X0.8+0.4MM) fire alarm cable · 1,61 ₾/m
- Unifire JE-H(ST)H...Bd FE 180/E30-E90 fire alarm cable 2X2X0.80 mm + 0.40 mm · 2,18 ₾/m
- Unifire J-Y(st)Y…Lg 1X2X0,80mm+0,40 mm fire alarm cable · 1,67 ₾/m
- Unifire JE-H(St)H...Bd FE 180 / PH 120 1X2X0,80 fire-resistant fire alarm cable · 2,49 ₾/m
Fire alarm cables 2×2×0.8 mm + 0.4 mm: HUNKAKABLO J-Y(ST)Y, a screened signal cable with PVC insulation, foil screen and 0.4 mm drain wire, and Unifire JE-H(ST)H...Bd FE 180/E30-E90, a halogen-free fire-resistant cable that keeps working in fire for 180 minutes.
Both cables are for fire alarm loops, detectors and call points, but their purpose differs: J-Y(ST)Y is an ordinary signal cable for detection lines where the cable does not need to work during a fire, while JE-H(ST)H FE180 E30–E90 is for lines that must keep working in a fire, such as sounders, evacuation announcement, smoke extraction and fire suppression control. FE 180 means the cable carries current in fire for 180 minutes, and E30/E90 is the operating time of the system together with its fixings. A halogen-free (H) sheath gives off no toxic smoke when burning and is required in public buildings. Cable can be bought by the metre or by the reel with delivery in Tbilisi in 2–3 business days.
Also searched as: fire alarm cable, fire resistant cable, J-Y(ST)Y, JE-H(ST)H FE180
Guides
- Wired or wireless fire alarm for business in Georgia
- Fire alarms for business in Georgia: requirements, fines and choosing a system
- Fire detectors for home and business: standalone, Ajax or addressable
Frequently asked questions
What does 2×2×0.8 + 0.4 mm mean?
Two twisted pairs (four conductors) with 0.8 mm diameter copper cores and a 0.4 mm drain wire that touches the foil screen. A 0.8 mm diameter is about 0.5 mm² cross-section, the standard for fire alarm loops.
How does J-Y(ST)Y differ from JE-H(ST)H FE180?
J-Y(ST)Y is a PVC cable, protected against interference but quick to burn in fire; it is used on detection lines. JE-H(ST)H FE180 is fire-resistant, halogen-free and works in fire for 180 minutes, so it is needed for sounder, announcement and control lines where regulations require it.
How should the screen be earthed?
The screen is earthed through the drain wire at one end only, usually at the fire panel. Earthing at both ends creates a loop and increases interference; at the detectors the screen must continue unbroken from one section to the next.